Flame Retardancy Rating Selection for Fire and Security System Cables: Engineering Judgment from FPLR to PH120
2026/09/18 30

Fire and security cable selection follows the principle of "installation position determines rating, building type determines duration": vertical riser installation between floors requires the FPLR rating; circuits that must maintain power during a fire should select PH30/PH60/PH120 fire resistance durations based on building importance, consistent with fire protection design documents and acceptance requirements.

Related Topics

  • How to Select Fire Cable Ratings
  • Difference Between PH60 and PH120
  • Security Monitoring Cable Requirements
  • Fire Acceptance Cable Standards
Flame Retardancy Rating Selection for Fire and Security System Cables: Comparison Chart for Engineering Judgment from FPLR to PH120

Fire cable compliance cannot be remedied after the fact. The selection phase must be strictly aligned with fire protection design documents.

1. Two Dimensions of Ratings

  • Installation dimension: FPL (general areas), FPLR (Riser, vertical installation in risers/between floors).
  • Time dimension: PH30 / PH60 / PH120, indicating the duration of circuit integrity under flame conditions.

2. How to Determine Fire Resistance Duration

Building/Facility TypeCommon RequirementsDescription
Fire linkage in general civil buildingsPH30Basic alarm and linkage circuits
Important fire facilities and evacuation systemsPH60Requires longer maintenance duration
Super high-rise and important public buildingsPH120Key fire facilities maintained for 120 minutes

Specific requirements are subject to the project's fire protection design documents and local acceptance standards.

3. Cable Characteristic Requirements

  • Outer layer wrapped with flame-retardant material, effectively slowing burning speed and ensuring safe use.
  • High-temperature resistant with strong flame resistance.
  • Applied in fire alarm systems, security monitoring equipment, automotive electronics, and other fields.

4. Construction Quality Determines Fire Resistance

  1. Fire protection lines are installed independently, not sharing trays with strong-current wiring.
  2. Fire stopping where lines cross fire compartments.
  3. Maintain fire resistance continuity at joints to avoid weak points.
  4. Use fire-resistant supports for fasteners to prevent cable falling during fires.

5. Common Reasons for Acceptance Rejection

  • Cable rating does not meet design requirements (e.g., FPL misused in risers).
  • Missing certification certificates or test reports.
  • Unclear printing, making model and manufacturer untraceable.
  • On-site sampling re-inspection failure.

Fahua Cable Supply

Fire alarm and security cables covering UL FPL, FPLR, and PH30 / PH60 / PH120, with certification documents and test reports available, supporting project acceptance documentation. Tel: 0574-65837193.

Updated: 2026-09-18 | Sources: Xiangshan Fahua Cable product specifications and public certification documents

Previous: Analysis of Common Cable Failure Causes: Temperature Rise, Insulation Aging, Terminal Crimping, and Mechanical Stress Next: Why Medical and Robotic Equipment Need "Extra-Flexible" Cables: Analysis of Ultra-Fine Copper Stranding Process
Home

Home

Products

Products

About Us

About Us

News

News

Contact Us

Contact Us

Phone

+86 13705747330

WeChat

QR Code

QR Code

Inquiry